T Type Strainer: What The Straight Body Buys You

The screen sits in the run, not in a pocket

A Y type strainer pushes the screen into a branch set at an angle to the line. The flow has to turn to reach it, the screen is small against the bore, and what it catches sits in the same narrow pocket the flow has to pass. A T type is built the other way round: the body is a straight run with a full branch at right angles, the screen is a cylinder held in that branch, and the branch ends in a cover above and a drain below. The screen separates the branch from the bore, so the dirt stays on the branch side and falls into the pocket under it.

What the straight body buys

The screen can be much larger than the bore at the same nominal size, so the velocity through the mesh is lower, the pressure drop is lower, and the mesh is less likely to be pushed through by the differential across it. The pocket under the screen is a settling space: debris that arrives in a burst drops out of the flow instead of being held against the mesh, and a blowdown valve on the drain empties it without opening the body. The screen also comes out upward through the cover, so cleaning does not mean breaking either flange joint.

What it costs

The body is longer and heavier than a Y type at the same size, and it needs clear space above the cover for the screen to be withdrawn, a dimension easy to leave out of a layout and hard to find afterwards. The branch is also a dead pocket, so a line carrying solids, or water that can sit, has to be drained, and a strainer on a line that must stay online needs a bypass. The price is higher, which is why Y types survive on light dirt loads.

Where it belongs, and where it does not

It belongs where the dirt load is heavy or arrives in bursts: commissioning a new line, upstream of a control valve, a trap station or a pump, and on services where the screen will be opened often. It does not belong in a horizontal gap between two flanges with no room above, on a vertical run with nothing to stand on, or on a line nobody will ever open; there the alternative is a basket body or a Y type with a coarse screen.

Installation rules that decide whether it works

The arrow on the body is not a suggestion. Cover up, drain down; a T strainer laid on its side has a pocket that collects nothing and a screen that cannot come out. Put a valve on the drain and pipe it where the discharge can be seen, because a blowdown that empties onto the floor will not be used. Fit gauge connections either side, because differential pressure is the cleaning signal and the calendar is not. Do not use the body as a pipe support or as a way to pull two flanges together.

Mesh, open area and what the number means

The mesh number describes the screen, not the filtration: the aperture at a given mesh depends on wire diameter and weave, and the screen maker states it. Coarse screens go on steam and on large flows where the target is weld slag and scale; finer screens go where the target is instrument lines, traps and small trim. A finer mesh on the same body raises the pressure drop and shortens the interval between cleanings, and past a point the screen itself becomes the restriction. What should be specified is the open area of the screen against the pipe, and the differential pressure at which the element is cleaned or replaced.

Body material and what the numbers cover

Cast carbon steel covers ambient service; LCB, the low temperature carbon steel to A352, takes the same body down to −46 °C, so a cold line does not need a stainless body for filtration alone. Screens are 304 or 316 stainless. The body is designed to B16.34, flanged to B16.5 with a raised face, offered from Class 150 to 600 and from PN10 to PN64, in sizes from DN50 to DN600, and pressure tested to API 598. The temperature ceiling is set by the body material and the cover gasket, not by the screen.

How they fail

What you see What happened What to do
Screen collapsed or torn Differential across the element went past what it can carry Clean on pressure drop, not on a schedule; larger body or coarser mesh
Screen blind in a few days No blowdown, or the blowdown valve is never opened Size the drain for the flush available, pipe it to sight
Debris still reaching the seat downstream Screen fitted the wrong way, or the cover gasket is bypassing Mark the element, one gasket, check the seating face
Wall loss in the pocket below the screen Water sitting in the branch, or condensate in steam service Drain after every cleaning; keep the blowdown valve working

What to put on the enquiry

Size and class in the standard the line uses, because a DN with a Class is not the same as an NPS with a rating; body material and the lowest temperature; screen material and mesh; drain size and whether it is threaded or flanged; whether gauge tappings are wanted; medium and temperature; and whether the line is horizontal or vertical. Then say how it will be cleaned, by blowdown or element out, because that decides whether cover clearance and a bypass are needed. J-VALVES supplies cast steel and LCB T type strainers from DN50 to DN600 (2 to 24 inch) in Class 150, 300 and 600 and PN10 to PN64, with 304 or 316 screens in 20, 40, 60 or 80 mesh, raised face flanged to B16.5 and tested to API 598. The other half of the same decision is what sits downstream: a check valve closes on whatever the screen lets through, which is the subject of swash plate check valve.

Frequently Asked Questions

Is a T type strainer better than a Y type? Only where its advantages are used. It gives a larger screen at the same size, a settling pocket and a blowdown, and it lets the screen be pulled without breaking a flange joint, at the cost of length, height and price. A Y type is compact, cheap, and right for light dirt loads in tight space.

Can a T type strainer be installed vertically? The body can be, but the branch holding the screen and the pocket must still point down and the screen must still come out upward, which on a vertical run usually means a short horizontal spool and a support.

How often should the screen be cleaned? When the differential pressure reaches the value written in the operating procedure, not on a calendar: record the clean baseline at commissioning at the design flow, and clean at two or three times that figure.

Manufacturer and supplier of industrial valves, including Floating Ball Valves, Trunnion Ball Valves, Flanged Gate Valves, Welded Gate Valves, High Pressure Gate Valves, Globe Valves, Swing Check Valves, Double Disc Wafer Check Valves, Y Strainers , etc. For more information, please send us your email .

QUICK LINKS

PRODUCTS

CONTACT US

Tel:+86 15158426559
Fax:0086 577 56692524
WhatsApp:+86 13600648865
Address:Wenzhou China
Ball Valves,Gate Valves,Globe Valves,Check Valves,Butterfly Valve,Strainer.
Copyright © 2020 J-VALVES. All Rights Reserved | Support by Leadong | Sitemap |  Privacy Policy